we need to pay attention to when repairing fire extinguishers? Next, let Fujie Fire Equipment explain to you:
1. Before disassembling the fire extinguisher, it can only be disassembled after confirming that there is no pressure inside the extinguisher, and safe disassembly methods and necessary safety protection measures must be adopted.
2. When cleaning up residual fire extinguishing agents in fire extinguishers and filling them with new fire extinguishing agents, it is necessary to prevent contamination caused by mixing different fire extinguishing agents.
3. When repairing gas cylinder type fire extinguishers, regardless of whether the gas cylinder is used or not, it should release all carbon dioxide. Each gas cylinder should be subjected to a water pressure test, cleaning, drying, sealing replacement, carbon dioxide filling according to regulations, and airtightness testing one by one.
Fujie Fire Equipment Analysis Fire Extinguisher Maintenance Procedure:
1. Conduct a visual inspection of the fire extinguisher to confirm its specifications and model, as well as whether it falls within the scope of scrapping;
2. Check the internal pressure of the fire extinguisher and disassemble it when confirming that there is no pressure inside the fire extinguisher;
3. Scrap fire extinguishers that have been confirmed to be within the scope of scrapping;
4. Conduct water pressure tests on each fire extinguisher cylinder, gas storage cylinder, nozzle, and spray hose assembly of wheeled fire extinguishers that are confirmed to be not within the scope of scrapping;
5. Clean the fire extinguisher cylinder and use dry powder, carbon dioxide, and clean gas fire extinguishers after drying the cylinder;
6. Inspect fire extinguisher accessories, replace seals and damaged components;
7. Recharge the fire extinguishing agent and driving gas according to the corresponding standards and nameplate of the fire extinguisher, and conduct airtightness tests one by one;
8. Conduct maintenance and factory inspection on the repaired fire extinguishers, and affix a maintenance certificate upon passing the inspection before leaving the factory;
9. Organize maintenance records.
|